FC 5037
| Penetrating Item(s): | |
| Base material: | |
| Fire rating: | 1 or 2 hour |
| Firestop product(s): |
System data
1. WOOD FLOOR/CEILING ASSEMBLY (UL/ULC CLASSIFIED L500 SERIES)(1-HR. OR 2-HR FIRE-RATING) (2-HR SHOWN)
2. LUMBER OR PLYWOOD SUBFLOOR WITH FINISH FLOOR OF LUMBER,
PLYWOOD, OR FLOOR TOPPING MIXTURE.
3. PENETRATING ITEM TO BE ONE OF THE FOLLOWING
A. MAXIMUM 2'' NOMINAL DIAMETER STEEL PIPE (SCHEDULE 10 OR
HEAVIER)
B. MAXIMUM 2'' NOMINAL DIAMETER COPPER PIPE.
4. MAXIMUM 3/4'' THICK AB/PVC FLEXIBLE FOAM INSULATION
5. MINIMUM 3/4'' DEPTH HILTI FS-ONE INTUMESCENT FIRESTOP
SEALANT.
6. HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT INSTALLED INTO
ANNULAR SPACE TO FILL VOID TO MAXIMUM EXTENT POSSIBLE
NOTES
1. MAXIMUM DIAMETER OF OPENING = 5''
2. ANNULAR SPACE = MINIMUM 1/2'', MAXIMUM 1''
3. CHASE WALL- THE THROUGH PENETRANT MAY BE ROUTED THROUGH
A 1-HR. OR 2-HR. FIRE-RATED GYPSUM CHASE WALL