FC 5036
| Penetrating Item(s): | Insulated Pipe |
| Base material: | Wood Floor |
| Fire rating: | 1 hour |
| Firestop product(s): |
System data
1. WOOD FLOOR/CEILING ASSEMBLY (UL/ULC CLASSIFIED L500 SERIES)(1-HR. FIRE-RATING) (2-HR SHOWN)
2. LUMBER OR PLYWOOD SUBFLOOR WITH FINISH FLOOR OF LUMBER,
PLYWOOD, OR FLOOR TOPPING MIXTURE.
3. PENETRATING ITEM TO BE ONE OF THE FOLLOWING
A. MAXIMUM 2'' NOMINAL DIAMETER STEEL PIPE (SCHEDULE 10 OR
HEAVIER)
B. MAXIMUM 2'' NOMINAL DIAMETER COPPER PIPE
4. MAXIMUM 1-1/2'' THICK GALSS-FIBER PIPE INSULATION
5. MINIMUM 3/4'' DEPTH HILTI FS-ONE INTUMESCENT FIRESTOP
SEALANT
6. MINIMUM 5/8'' DEPTH HILTI FS-ONE INTUMESCENT FIRESTOP
SEALANT.
NOTES
1. MAXIMUM DIAMETER OF OPENING = 6-5/8''
2. ANNULAR SPACE= MINIMUM 1/2'', MAXIMUM 1''
3. CHASE WALL THE THROUGH PENETRANT MAY BE ROUTED THROUGH A
1-HR FIRE-RATED GYSPUM CHASE WALL
Downloads
| FC 5036 | |
| California State Fire Marshal Approval for FS-ONE High Performance Intumescent Firestop Sealant | |
| Material Safety Data Sheet for FS ONE Intumescent Firestop Sealant | |
| MEA for FS One Intumescent Firestop Sealant (New York City) | |
| Firestop Specification 07840 (General Firestopping) | |
| Firestop Specification 07840 (short form, General Firestopping) | |
| Through Penetration Firestop Systems |